Products - Control Panels

EV-301+ EV-601 Instruction Manual
EV-301 & EV-601 instruction manual. Contents: Dimensions - Page 4-6 Technical Information - Page 7-8 Product Descriptions - Page 9 Functional Specific...
Is it possible to set a service timer?
By default, the maintenance counter is disabled, this is possible by the programmable SIMON LINK software only available to trained personnel. See the...
How many actuators can be run from 1 Ev-301/EV-601 control panel?
If a chain drive is 1.4A you could run 2No on an EV-301 (2.8A total used) or 4 on an EV-601 (5.6A total) our 1000N folding arm is 3A, so it would need...
How do I wire my actuator into the EV-301/EV-601 Control Panel?
Please check the wiring guide in the O&M page 22 for SP Mode & page 24 for EV Mode.
How do I know if my EV-601/EV-301 Control Panel is in ‘fault’?
Operational status indicators (OK, Alarm & Fault) are shown on the HE-077 or relevant switch and listed in the O&M page 10 section 4.3.5.
If my EV-601/EV-301 Control Panel is in 'fault', how do I understand the fault?
The Fault LED consists of a series of short (*) and long (---) flashes with a long pause before the sequence is repeated, a full list of fault sequenc...
Do the panels offer open & close vent delay?
Please see O&M page 11 section 5.4 & 5.5
How do I wire a Wind/Rain sensor to an EV-301/EV-601 Control Panel?
In SP Mode, please refer to the O&M page 22, figure 15. For EV-Mode Page 24, figure 30
Can the switch input work as a dead-man function?
Please see O&M page 14 section 6.3.1 & 6.3.2
How do I wire a thermostat to an EV-301/EV-601 Control Panel?
In SP Mode, please refer to the O&M page 22, figure 14. For EV-Mode Page 24, figure 28
Do the panels offer gap ventilation?
Please see O&M page 14 section 6.3.3 & 6.3.3.a
How do I know if my panel is in EV or SP mode?
Please check the Jumper link JP1 position on the main PCB, if removed the panel is in SP-Mode, please ensure Dip switch 10 is in the ‘ON’ position if ...
I have replaced the batteries and it’s still showing a battery/power fault?
Please check the Jumper link JP2 position on the main PCB, please remove the jumper JP2 to enable the battery operation. See O&M page 11, section 5....
Do the panels have a timed ventilation setting?
Please see O&M page 14 section 6.3.4 & 6.3.4.a]
Can I use the EV-301/EV-601 control panels for daily ventilation?
The switch inputs can also be used with a thermostat if required. Please refer to the O&M page 14 section 6.3.
How do I interconnect control panels?
Please note that works on the equipment should only be carried out by a qualified and competent electrical person as there is a high risk of electrocu...
Do I need to provide access to the panels for maintenance?
Yes. It is good practice to install the panels in accessible locations for future maintenance.
Do I need a switch at the top and the bottom of the stairs?
While Approved Document B of the building regulations only states that a Fireman’s Override Switch (FOS) is required at the bottom of the stairs, it...
Where do I connect sprinkler system to EV-301?
This is only applicable in EV mode. Please contact us for more information. Please note that works on the equipment should only be carried out by a...
Do you have just DV panels?
Yes, please see our control panels page for more information.
How do I wire an EV-301/601?
You can find detailed instructions on how to wire the EV-301 or the EV-601 in their respective datasheets. Please note that works on the equipmen...
How do I connect a fire alarm interface to an EV-301 / EV-601?
You can find detailed instructions on connecting a fire alarm interface to the EV-601 Control Panel in the O&M page 22, figure 8 for SP mode & page ...
Do I have to connect the system to a fire alarm system?
Connection to a fire alarm system is not specified in the standards and whether this is required or not is normally stipulated by building control/fir...
Can I use EV-301/EV-601 for DV functions?
Yes, you can. See the O&M for full DV functionality page 14 section 6.3. Please note that works on the equipment should only be carried out by a qua...
Can I install the EV-301/EV-601 panel in the smoke shaft?
No. The EV-301/EV-601 panels should be installed out of the fire zone or in a fire-rated riser adjacent to the smoke shaft rather than in the shaft it...
How many cores do I need to install between the panel and the fireman’s switch?
3 core cables are required between the panels and Fireman’s Override Switch (FOS).
Where can I buy HE075/HE076 switches from?
The HE075/HE076 switches have been discontinued and you cannot purchase them anymore. We do however stock the  HE-077 Fireman’s Override Switch , the ...
What is the difference between the EV and SP mode on the EV 301/601 control panels?
Simple Natural Ventilation (SP Mode) and Advanced Shaft System (EV Mode). You can find the EV-301+EV-601 Wiring details for SP Mode on the EV-301 or...
Do I need to buy a switch?
Yes. The Fireman’s Override Switch (FOS) is required for use by fire officers on entry to the building and provides an indication of the status of the...
Can you replace a SP-300 panel with an EV-301 panel?
Yes, you can. Follow this link to download the replacement instructions.
I have 230V smoke detectors installed. Can I use these to trigger the EV-301/EV-601?
If the 230V smoke detectors have relay outputs then it should be possible to connect these to the panels using the fire alarm inputs.
What is the best solution for replacing a SP-200 system?
If you have a large system consisting of SP-200 control panels, you can buy spare parts here. If you are looking to replace a standalone SP-200, we re...
What can I replace a SP-300 control panel with?
You can replace a SP-300 with an EV-301 control panel. Find out more on the product page.
Where can I buy spare parts for the W1 (W1/1001) system from?
The W1 System is obsolete and spares for it are no longer sold and supported. You will need to replace the entire system. You can see our full range o...
How many smoke detectors can I connect to a single EV-301/EV-601 panel?
8 smoke detectors can be connected to a single Control Panel using 2 core + E CAT 3 cable.